1901
What This Code Means
Undervoltage (both zero crosses missing for 1.5 seconds); Undervoltage (little / no voltage, <120V); Undervoltage (no field current but have DPE); Generator Shuts Down for Under Voltage; No RPM pulses sensed for 75 consecutive milliseconds while starter active; Cranking faults to RPM sensor loss; Starter engaged, no tooth pulses for 75 ms; While running, no tooth pulses for 75 consecutive milliseconds; Unit Overloaded or Fuel System issue; Low Fuel Pressure; Throttle Stuck Closed/near Closed; Undervoltage; No pulse during cranking (RPM sensor); No tooth pulses sensed for 75 consecutive milliseconds while starter active; No pulse during running (RPM sensor); Loss of RPM sensor signal while running; Missing pulses during cranking (RPM sensor); Missing pulses during running (RPM sensor); Underspeed condition detected (<83.3% speed (60 Hz) or <66.6% speed (50 Hz) for 30 seconds); Unit overloaded slowing engine speed; Underspeed condition detected; Low fuel pressure detected for 1200 ms bef
Possible Causes
- •AVR voltage communication failure or incorrect voltage reported via communication line
- •AVR voltage information sent to Evolution controller via communication lines
- •AVR voltage reported low to controller via communication line for 10+ seconds
- •AVR voltage reported low via communication line
- •Brush failure
- •Circuit in general
- •Communication line issue between AVR and Evolution controller
- •Controller measuring no voltage
- •Faulty AC Sensing Circuit
- •Faulty Brushed Rotor Assembly
- •Faulty DB1 Diode
- •Faulty DB2 Diode
- •Faulty DPE Breaker
- •Faulty DPE Circuit
- •Faulty Fixed Excitation Circuit
- •Faulty Flash Wiring
- •Faulty Main Circuit Breaker
- •Faulty Regulator Output
- •Faulty Rotor Insulation Resistance
- •Faulty Stator
- •Faulty excitation winding
- •Faulty zero cross circuit
- •Field boost hardware failure
- •Loose wiring
- •Low voltage condition for 10+ seconds
- •Low voltage condition sustained for 10+ seconds
- •Undervoltage
- •Undervoltage reported from AVR via communication line for 10+ seconds
- •Undervoltage reported to controller from AVR via communication line
- •Undervoltage value reported from AVR via communication line for 10+ seconds
- •Undervoltage value reported to Evolution controller
- •Undervoltage value reported to Evolution controller from AVR via communication line
- •Voltage reported to the controller from the AVR via communication line is low for 10+ seconds
- •Wire loose
Suggested Actions
- 1Check communication wires between AVR and Evolution controller
- 2Perform Rotor Insulation Resistance Test
- 3Perform Test 2
- 4Repair or Replace Rotor
- 5Repair or Replace Wire 14
- 6Replace Controller
- 7Replace Rotor Only
- 8Replace Rotor and Stator
- 9Replace Stator Only
- 10Test AC Sensing Circuit
- 11Test Brushed Rotor Assembly
- 12Test DB1 Diode
- 13Test DB2 Diode
- 14Test DPE Breaker
- 15Test DPE Circuit
- 16Test Field Flash Circuit
- 17Test Fixed Excitation
- 18Test Flash Wiring
- 19Test Main Circuit Breaker
- 20Test Regulator Output
- 21Test Stator
- 22Test Wire 14 Field Flash Circuit
- 23Verify Generator output voltage in the Dealer Menu display of the Evolution controller