1800

UnclassifiedLubrication

What This Code Means

Generator produces low voltage at no-load; Generator shuts down for overload; Generator shuts down for over voltage; No RPM pulses sensed for 75 consecutive milliseconds while starter active; Cranking faults to RPM sensor loss; Starter engaged, no tooth pulses for 75 ms; While running, no tooth pulses for 75 consecutive milliseconds; Unit Overloaded or Fuel System issue; Low Fuel Pressure; Throttle Stuck Closed/near Closed; No pulse during cranking (RPM sensor); No tooth pulses sensed for 75 consecutive milliseconds while starter active; No pulse during running (RPM sensor); Loss of RPM sensor signal while running; Missing pulses during cranking (RPM sensor); Missing pulses during running (RPM sensor); Underspeed condition detected (<83.3% speed (60 Hz) or <66.6% speed (50 Hz) for 30 seconds); Unit overloaded slowing engine speed; Underspeed condition detected; Low fuel pressure detected for 1200 ms before underspeed; Throttle stuck closed or near closed; Limiting fuel to the engine, s

Possible Causes

  • Fuel supply problem
  • Shorted condition in a connected load
  • Shorted condition in one of the load circuits
  • Heavy capacitive load
  • Starter circuit issue
  • RPM sensor loss
  • RPM sensor alignment
  • Low battery
  • Unit is overloaded slowing engine speed
  • Highly inductive loads
  • Low fuel pressure starves the engine, slowing it.
  • Low fuel pressure detected for 1200 ms before underspeed condition detected.
  • The throttle is stuck closed or stuck near closed limiting the fuel to the engine, slowing it down.
  • Stuck closed must be detected for one second with underspeed to set E-Code.
  • RPM sensor issue
  • RPM sensor alignment issue
  • Low fuel pressure starving the engine
  • Throttle stuck closed or near closed
  • Overspeed generator
  • Actuator

Suggested Actions

  1. 1Correct the fuel supply
  2. 2Open all load breakers and bring them on one at a time to determine which branch circuit is the cause of the problem.
  3. 3Refer to Problem 31 for RPM Sensor troubleshooting
  4. 4Check fuel supply and settings
  5. 5Test 68
  6. 6Problem 31
  7. 7Problem 3
  8. 8Refer to Problem 3 – Generator Shuts Down for Overload / Overvoltage page 55
  9. 9Check the inlet/outlet for debris.
  10. 10Check coolant sensor circuit for proper operation.