1802

UnclassifiedElectrical

What This Code Means

Generator produces low voltage at no-load; Generator shuts down for overload; Generator shuts down for over voltage

Possible Causes

  • Fuel supply problem
  • Shorted condition in a connected load
  • Shorted condition in one of the load circuits
  • Heavy capacitive load

Suggested Actions

  1. 1Correct the fuel supply
  2. 2Open all load breakers and bring them on one at a time to determine which branch circuit is the cause of the problem.