1511

UnclassifiedCooling

What This Code Means

Shutdown Alarm/ Fault Occurred During Crank Attempt, Start or Run; NO CRANK; Wiring Continuity Issue (Wire 18); LOW OIL PRESSURE; HIGH OIL TEMPERATURE; OVERCRANK; LOW BATTERY; IGNITION SPARK ISSUE; SHUTDOWN WIRE ISSUE; OVERSPEED; RPM SENSE LOSS; CRANK; NO CRANK CODE; RUNNING E-CODE; LOW OIL PRESSURE E-CODE; HIGH TEMP E-CODE; OVERCRANK E-CODE; OVERSPEED E-CODE; RPM SENSE LOSS E-CODE; CRANK E-CODE; Engine shutdown; Loss of engine ignition; Fuel shutoff solenoid closure; Engine shutdown and latch out; RPM Sensor Loss; Engine re-cranks

Possible Causes

  • •BAD
  • •BAD NO SIGNAL
  • •Closure of the fuel shutoff solenoid
  • •Controller does not see a valid rpm signal within three (3) seconds during cranking
  • •Controller does not see an RPM signal (will not energize Wire 14/Fuel Solenoid)
  • •Defective circuit board
  • •Engine speed exceeds approximately 72 Hz (4320 rpm)
  • •Faulty crank circuit
  • •Faulty starter
  • •Grounding of the ignition circuit
  • •Lack of engine cranking
  • •NO SIGNAL
  • •No rpm signal is detected within the first three (3) seconds of cranking
  • •RPM signal is lost for one full second during running
  • •RPM signal is subsequently lost again
  • •SHORTED WIRE 18 OR CIRCUIT BOARD
  • •Shorted Wire 18
  • •Shorted wire 18 or circuit board
  • •Temperature exceeds approximately 293 ºF (144 ºC)
  • •Wire 18 continuity fault

Suggested Actions

  1. 1CHECK INSTALLATION FOR PROPER AIRFLOW
  2. 2Clear any faults in the controller before proceeding with any running diagnostic steps
  3. 3Clear any faults in the controller before proceeding with diagnostic steps
  4. 4Controller attempts one re-crank attempt before latching out
  5. 5Controller waits 15 seconds, then re-cranks the engine
  6. 6Engine speed returns to normal operation (implicit, as the shutdown is to protect from overspeed)
  7. 7FOLLOW PROCEDURE IN APPENDIX B
  8. 8Go to Problem 16
  9. 9Go to Problem 17
  10. 10PROCEED TO PROBLEM 17
  11. 11PROCEED TO TEST 45
  12. 12Proceed to Problem 16
  13. 13REPAIR OR REPLACE DEFECTIVE SWITCH
  14. 14REPAIR OR REPLACE SHORTED WIRE 18 OR CIRCUIT BOARD
  15. 15Repair or replace shorted Wire 18 or circuit board
  16. 16Repair or replace shorted wire 18 or circuit board
  17. 17TEST 12 – CHECK STEPPER MOTOR CONTROL
  18. 18TEST 55 – CHECK FOR IGNITION SPARK
  19. 19TEST 59 – CHECK SHUTDOWN WIRE
  20. 20TEST 60 – CHECK IGNITION MAGNETOS
  21. 21TEST 61 – CHECK OIL PRESSURE SWITCH AND WIRE 86
  22. 22TEST 62 – CHECK HIGH OIL TEMPERATURE SWITCH
  23. 23TEST 64 – CHECK WIRE 18 CONTINUITY
  24. 24Test 64 – Check Wire 18 continuity
  25. 25Test 64 – Check wire 18 continuity
  26. 26Wait for temperature to return to a safe operating level (engine will automatically restart, fault on LCD display will reset)