004944
UnclassifiedElectrical
What This Code Means
Incorrect output voltage at the breaker; Output voltage at the breaker is not consistent within 5 volts of the value displayed in the controller TEST menu; Generator shuts down for under voltage
Possible Causes
- •Calibration factor adjusted outside of the window (990-1040)
- •Damage to the generator due to incorrect calibration adjustment
- •Incorrect voltage output was not achieved using the specified calibration window
Suggested Actions
- 1Adjust the calibration setting using UP or DOWN arrows
- 2Ensure the calibration setting is within the 990-1040 window
- 3Press ENTER to save the new setting
- 4Perform the Field Boost Test (FBT) if a correct voltage output was not achieved within the specified window
- 5Perform the Field Boost Test (FBT)
- 6Refer to Problem 1 – Generator Shuts Down for Under Voltage
Related Generac Fault Codes
ASK RUDY ABOUT THIS FAULT
Get a diagnosis walkthrough for 004944 on your specific Generac unit — cited to the OEM manual, not a forum guess.
TRY IT FREE