TRANSFER FAIL
What This Code Means
TSC 900 Transfer Fail alarm activated; Will not re-transfer to utility source upon restoration; Will not transfer to generator source upon failure of utility source; Transfer to generator source without a power failure in the utility source; Forced transfer to the generator supply is activated; Generator start signal is initiated; Load transfers to the generator supply; Re-transfer back to the utility supply does not occur; ‘On Utility’ LED flashes; ‘Alarm’ LED is activated; Alarm output signal on customer terminals #5 & #6 is activated; Forced transfer to the utility supply is activated; Load automatically transfers to the utility supply; Re-transfer back to the generator supply does not occur; ‘On Gen’ LED flashes; Forced transfer to the generator supply; Re-transfer back to the utility supply will not occur; 'On Utility' LED flashes; 'Alarm' LED activated; Forced transfer to the utility supply; Re-transfer back to the generator supply will not occur; 'On Gen' LED flashes; Fail to ex
Possible Causes
- •ATS Power Chassis & Voltage Sensing Isolation Plugs (PL12 or PL15) are unplugged
- •Defective Power contactor unit close coil
- •Defective Power contactor unit trip coil
- •Utility Return Time delay period in TSC 900 has not yet expired
- •A Load Test mode has been activated locally or remotely
- •An Exercise Test mode has been activated by the TSC 900 scheduler
- •Utility supply is not operating at correct voltage or frequency levels
- •TSC 900 has incorrect utility voltage or frequency settings for the ATS
- •Utility Phase Rotation is not matched with Generator supply (first time transfer)
- •TSC 900 connection plugs are unplugged (J1,2,3,4)
- •TSC 900 has 'Transfer Fail' alarm activated
- •Faulty Power contactor unit
- •A loose control wire connection
- •Defective TSC 900 controller
- •Faulty Power Contactor unit auxiliary contact
- •Transfer Mode selector is not in "Auto" position
- •A Transfer Inhibit signal has been activated
- •Warm-up time delay function has not timed out yet
- •Generator set output circuit breaker which feeds ATS is open
- •TSC 900 has incorrect generator voltage or frequency settings for the ATS
Suggested Actions
- 1Verify both PL12 & PL15 connectors are fully inserted
- 2Determine cause of alarm and rectify before TSC 900 is reset on GHC
- 3Refer to Power Contactor unit Troubleshooting Section
- 4Verify TSC 900 time delay setting
- 5Check TSC 900 GHC Home Page status indicators
- 6Check TSC 900 GHC Scheduler page
- 7Verify correct nominal levels the utility source should be operating at and compare to TSC 900 settings for under/over voltage, voltage phase balance and under/over frequency
- 8Re-Program TSC 900 with correct settings as required for voltage or frequency
- 9Check Generator & Utility Voltage Phase rotation matches on TSC 900 GHC Utility & Generator Voltage Pages. If power cabling has non-matching phase rotation, reverse power conductors on one phase on one of the supplies
- 10Verify all TSC 900 connectors are fully inserted
- 11Check all wiring connections in the ATS
- 12Verify TSC 900 has 120VAC control power applied to the utility control power input (J1
- 13Verify Generator & Utility auxiliary contacts are operating correctly. If defective, return to Thomson Power Systems using RMA process
- 14Turn Transfer Mode selector to "Auto" position
- 15Check TSC 900 indicators if a utility transfer inhibit signal has been activated and reset
- 16Verify TSC 900 timer setting
- 17Close generator set output circuit breaker
- 18Verify correct nominal levels the generator should be operating at and compare to TSC 900 Settings for under/over voltage, voltage phase balance, and under/over frequency
- 19Turn Transfer Mode selector to “Auto” position
- 20Verify TSC 900 has 120VAC control power applied to the generator control power input (J1 - 12, 13) and Diagnostic green LED is flashing