RED LED
UnclassifiedElectrical
What This Code Means
Generator voltage starts to become unstable; Red LED illuminates; Generator speed falls below a presettable threshold (knee point)
Possible Causes
- •Stability control turned too far anti-clockwise
- •Generator frequency falls below nominal (i.e., 47Hz on a 50Hz system or 57Hz on a 60Hz system)
Suggested Actions
- 1Run the generator at no load and slowly turn the stability control anti-clockwise until voltage becomes unstable, then turn it slightly clockwise to the optimum/critically damped position where volts are stable
- 2Select the correct 50 or 60Hz and 4 pole or 6 pole settings using the jumper link
Related Blue Star Power Systems Fault Codes
ASK RUDY ABOUT THIS FAULT
Get a diagnosis walkthrough for RED LED on your specific Blue Star Power Systems unit — cited to the OEM manual, not a forum guess.
GET THE ANSWER
Free account required — we'll bring your question with you.