MSC DATA ERROR
UnclassifiedElectrical
What This Code Means
Affected genset declares 'MSC ID ERROR'; Electrical trip on the affected set; Affected modules display 'MSC DATA ERROR'; Operation of the MultiSet system is not possible; MSC failure alarm occurs (configured as a warning or electrical trip)
Possible Causes
- •Two or more gensets have the same MSC ID
- •Data is corrupted on the MultiSet Communications link
- •Incorrect wiring used between the modules
- •MSC terminator is incorrectly enabled on non-end units or not enabled on end units
- •Maximum cable run distances are exceeded
- •The number of modules communicating on the Multiset communications link falls
Suggested Actions
- 1Set the correct ID using the PC configuration software
- 2Commission units starting with ID 1, 2, 3 etc. and configure spare modules as 16, 15 etc. to avoid conflicts
- 3Ensure correct wiring is used between the modules
- 4Enable the MSC terminator on only the end units on the link
- 5Ensure maximum cable run distances are not exceeded