MINIMUM GENSET FREQUENCY ALARM

UnclassifiedCooling

What This Code Means

Voltage values obtained between genset phases (VG12, VG23, or VG31) are under the minimum programmed limits; Genset frequency is under the minimum programmed frequency limits; No frequency signal detected on the first-phase, second-phase, or third-phase; Unexpected engine shutdown; Engine stop failure; Engine conditions are not detected 15 seconds after a stop attempt

Possible Causes

  • Voltage values between genset phases remain under the minimum programmed limits (Thresholds table parameter 3) during the programmed time (alarms table parameter 62)
  • Genset frequency values obtained are kept under the minimum programmed limits (Thresholds table parameter 6) during the stabilization time (alarms table parameter 65)
  • Controller fails to detect all engine starting conditions (regulations table parameters 19 to 22) while the engine is running
  • All engine conditions (regulations table parameters 19 to 22) are not detected within 15 seconds after an engine stop attempt

Suggested Actions

  1. 1Stop the engine with cooling (configured via alarms table parameter 63)
  2. 2Stop the engine with cooling (configured via alarms table parameter 66)
  3. 3Disconnect the stop failure alarm (alarms table parameter 70) to allow the device to consider the engine stopped after waiting 15 seconds
  4. 4Ensure all stopping conditions are detected during a programmed time (alarms table parameter 71) to successfully detect the engine stop