LED4
UnclassifiedGeneral
What This Code Means
Generator set shuts down; Fault lamp lights; LED4 lights; Generator set does not shut down during Low Oil Pressure (LOP) shutdown test
Possible Causes
- •Engine temperature exceeds 110 °C (230 °F)
- •Faulty control board
- •HET (High Engine Temperature Switch) contacts close
- •High coolant temperature (High Coolant Temperature Switch [HCT] closes completing path to ground)
- •High exhaust temperature (High Exhaust Temperature Switch [ETS] closes completing path to ground)
- •Incorrect calibration of the overvoltage shutdown setting
- •LCS (Loss of Coolant Switch) contacts close
- •LOP (Low Oil Pressure) shutdown switch contacts close
- •Loss of coolant (Loss of Coolant Switch [LCS] closes completing path to ground)
- •Low coolant level
- •Low oil pressure
- •Low oil pressure (Low Oil Pressure Switch [LOP] closes completing path to ground)
- •Oil pressure drops below 5 psi
- •Oil pressure drops below 5 psi (Low Oil Pressure switch closes)
- •Oil pressure drops below 5 psi for 5 seconds
Suggested Actions
- 1Check the continuity of the wiring harness leads before replacing the control board
- 2Repeat the calibration output procedure
- 3Replace the control board
- 4Slowly increase voltage and verify the shutdown setting by observing the voltmeter and noting when red LED4 lights
- 5Test procedure: Jump pin J4-13 of the controller harness to ground and verify shutdown after approximately 35 seconds
- 6Test the individual shutdown circuit components
- 7Turn the voltage adjustment potentiometer counterclockwise to reduce output voltage