INPHASE MONITOR (IPM) SYNCHING
UnclassifiedGeneral
What This Code Means
The two sources did not synchronize within the Fail to Sync time delay
Possible Causes
- •Generator set frequency misadjustment
- •Generator set frequency out of sync
- •Incorrect inphase monitor angle
- •Incorrect synchronization settings for voltage differential, frequency differential, or phase angle
- •Inphase monitor angle misadjusted
Suggested Actions
- 1Adjust inphase monitor angle
- 2Adjust the generator set frequency in order to achieve source synchronization
- 3Adjust the generator set frequency in order to achieve source synchronization (refer to Generator set manuals)
- 4Check synchronization settings for voltage differential, frequency differential, and phase angle (See TP-6714, MPAC 1500 Controller Operation Manual)
- 5Connect IPM Synching output to customer-supplied equipment to boost the generator set if the sources do not synchronize
- 6Set the programmed-transition override function to allow a programmed-transition transfer in the event that the sources do not synchronize