HICORE ON-SCREEN WARNING

UnclassifiedEmissions

What This Code Means

System does not run properly; Oscillations in the genset; HICORE displays an on-screen warning indicating that the generator set capacity is less than the minimum value

Possible Causes

  • Primary power supply does not meet the minimum power value required for the EHR model
  • Generator set power is lower than recommended
  • Power assist (PEAK SAVING) function is performed on more than 90% of the generator set capacity

Suggested Actions

  1. 1Ensure the primary electrical grid power supply meets the minimum requirements (EHR 20: 4.00 A / 3.00 kW; EHR 30: 11.00 A / 8.00 kW; EHR 45: 15.00 A / 10.00 kW)
  2. 2Ensure the generator set power supply meets the minimum power requirements (EHR 20: 20 kW; EHR 30: 30 kW; EHR 45: 45 kW)
  3. 3Perform the Power Assist (PEAK SAVING) function on 90% of the capacity of the generator set to avoid oscillations
  4. 4Ensure the generator set meets the minimum recommended power capacity (EHR 20: 20 kW; EHR 30: 30 kW; EHR 45: 45 kW)

ASK RUDY ABOUT THIS FAULT

Get a diagnosis walkthrough for HICORE ON-SCREEN WARNING on your specific Hipower Systems unit — cited to the OEM manual, not a forum guess.

TRY IT FREE