FAIL TO ACQUIRE PREFERRED SOURCE

UnclassifiedElectrical

What This Code Means

Problems with transfer switch operation; Preferred source does not reach acceptable voltage and stabilize within allowed time

Possible Causes

  • •Preferred source does not reach acceptable voltage and stabilize within the allowed time
  • •Preferred source fails to reach acceptable voltage and stabilize within the allowed time (default 1 min)

Suggested Actions

  1. 1Initiate a test and compare operation to the test sequence illustrated in the Unloaded or Loaded Test Sequence flowcharts
  2. 2Observe the controller display to identify which time delay is executing
  3. 3Use the View Time Delays screen to check the settings for the adjustable time delays