F1

UnclassifiedElectrical

What This Code Means

Voltage buildup does not occur; Regulator damage

Possible Causes

  • Incorrect polarity of the DC source
  • Flashing the field when the generator is in motion

Suggested Actions

  1. 1Verify the polarity of the DC source and repeat the field flashing steps with the prime mover at rest.
  2. 2Do not flash the field when the generator is in motion.
  3. 3Perform the field flashing procedure only when the prime mover is at rest.