EMERG STOP SHUTDWN
UnclassifiedStarting
What This Code Means
Generator set shuts down immediately; Engine cooldown cycle is bypassed; Controller emergency stop lamp lights; Generator set cannot be restarted; Controller display shows Emerg Stop Shutdwn
Possible Causes
- •Emergency stop button is activated
- •Remote emergency stop button is activated
- •Remote emergency stop button is locked in the STOP position
- •Shutdown switch is in the off (O) position
- •Shutdown switch is turned to the off (open, O) position
Suggested Actions
- 1Press I (On) on the shutdown switch to allow the engine to start and run
- 2Pull the remote emergency stop button out
- 3Remove the locking device from the emergency stop switch
- 4Reset the controller by pressing the OFF/RESET button
Related Rehlko Fault Codes