E1
UnclassifiedSpeed
What This Code Means
Display Code E1 active; Loss of remote speed potentiometer signal; Unable to modify parameters
Possible Causes
- •A display code is active (load share model)
- •Loss of Remote Set Speed Signal
- •Loss of remote speed potentiometer signal
- •Measured Remote Speed Signal input voltage is less than 0.20 VDC or greater than 4.8 VDC
- •Password protection is enabled (load share model)
- •The parameter’s value is the maximum value allowed
- •The parameter’s value is the minimum value allowed
Suggested Actions
- 1Enter Password
- 2Enter acceptable value
- 3Refer to the Display Codes section
- 4Remove power from the controller to clear the E1 error (when E1 Handler Select value is 0)
- 5Return Remote Set Speed Signal to the Speed Potentiometer Min or Speed Potentiometer Max position recorded during calibration to automatically clear the error (when E1 Handler Select value is 1)
- 6Set the E1 Handler Select parameter value to 2 to accept a 0.0 to +5 VDC remote speed signal