CHECK MODULE SETUP TO CLEAR FAULT

UnclassifiedGeneral

What This Code Means

Display shows Module Status Conflict message

Possible Causes

  • •One type of module is replaced with another type of module that has the same address

Suggested Actions

  1. 1Disconnect power to the transfer switch
  2. 2Disconnect the module
  3. 3Close the enclosure door and reconnect power to the ATS
  4. 4Press the button labelled Reset when display shows Module Status Change
  5. 5Follow the procedure in the Module Status Change section to uninstall the module through the ATS controller keypad when Check Module Setup to Clear Fault is displayed
  6. 6Disconnect power to the ATS
  7. 7Connect the new module
  8. 8Press the button labeled Reset to display Reset New Module, then press the reset button from that screen
  9. 9Navigate to the Set Auxiliary I/O screen to check the status and settings for the new module