BATTERY FLT
UnclassifiedElectrical
What This Code Means
Warning lamp on controller illuminates yellow; Alarm horn sounds; Local display shows Battery Flt
Possible Causes
- •Battery connection problem
- •Dead battery
- •Temperature rises above 60°C (140°F) or falls below -20°C (-4°F) when temperature compensation sensor is connected
- •Absorption timeout (battery unable to accept expected charge in given time frame)