AUXILIARY SWITCH OPEN
UnclassifiedSensors
What This Code Means
Main shaft auxiliary switches indicate ATS is in neither position; All switch inputs are open
Possible Causes
- •All main shaft auxiliary switch inputs are open
- •Controller cannot determine the transfer switch position
- •Main shaft auxiliary switches indicate all inputs are open
- •Main shaft auxiliary switches indicate that the ATS is in neither position (all inputs open)
- •Transfer switch in intermediate position
Suggested Actions
- 1Check the control contact operation
- 2Check wiring and connections to position microswitches
- 3Inspect for signs of coil damage or overheating and replace coil if necessary
- 4Manually operate the transfer switch
- 5Perform manual reset
- 6Press Reset button (Service Req'd Reset) to clear fault that triggered system alert LED
- 7Replace microswitch if necessary
- 8Test position microswitch operation