ALARMS TABLE PARAMETER 63
UnclassifiedElectrical
What This Code Means
Voltage values between genset phases (VG12, VG23, or VG31) are under the minimum programmed limits; Genset frequency is under the minimum programmed frequency limits; No frequency measurement signal detected on the first-phase, second-phase, or third-phase; Unexpected shutdown of the engine; Engine fails to stop (Stop failure)
Possible Causes
- •Genset phase voltage drops below the thresholds defined in Thresholds table parameter 3
- •Genset frequency values remain below the thresholds defined in Thresholds table parameter 6 during the stabilization time programmed in Alarms table parameter 65
- •The controller does not detect all engine starting conditions (regulations table parameters 19 to 22) while the engine is running
- •All engine stop conditions (regulations table parameters 19 to 22) are not detected 15 seconds after an engine stop attempt
Suggested Actions
- 1Stop engine with cooling (automatically triggered action configured by alarms table parameter 63)
- 2Stop engine with cooling (automatically triggered action configured by alarms table parameter 66)
- 3Disconnect the stop failure alarm (alarms table parameter 70) to allow the device to consider the engine stopped after waiting a maximum of 15 seconds
- 4Ensure all engine stopping conditions are detected during the programmed time (alarms table parameter 71)
Related Himoinsa Fault Codes
ALARMS TABLE PARAMETER 64ALARMS TABLE PARAMETER 65ALARMS TABLE PARAMETER 62ALARMS TABLE PARAMETER 66ALARMS TABLE PARAMETER 43ALARMS TABLE PARAMETER 70ALARMS TABLE PARAMETER 40ALARMS TABLE PARAMETER 71ALARMS TABLE PARAMETER 38ALTERNATOR VOLTAGE ALARMALARM TABLE PARAMETER 10 TO 12ALTERNATOR VOLTAGE ALARM (PARAMETER 10 TO 12)