4471-510

UnclassifiedCooling

What This Code Means

Bearing grease deterioration; Bearing grease loses lubricating properties; Premature bearing failure; Bearing temperature operating above recommended set points

Possible Causes

  • Extended service life (10 years of service in standby application under normal conditions)
  • High temperature environment
  • Condensing humidity
  • Coastal environment
  • Chemical environment
  • Abrasive environment
  • Generator set operating above recommended temperature set points
  • Lack of temperature monitoring and record-keeping

Suggested Actions

  1. 1Replace the bearing after 10 years of service in standby application under normal conditions
  2. 2Replace the bearing after 5 years of service if operated in harsh conditions (high temperature, condensing humidity, coastal, chemical, or abrasive environments)
  3. 3Measure the bearing temperature using an infrared thermometer after the generator reaches normal operating temperature
  4. 4Keep records to monitor the changes in the temperature of the bearing