32

UnclassifiedFuel

What This Code Means

Emergency Stop activated; Common Fault / Prealarm; Continuous cranking; Cyclic crank; Remote start activated; Common fault activated; Pre-alarm activated; Low fuel indicated; Battery charger fault indicated; Low battery volts indicated

Possible Causes

  • •AOP
  • •AOP activated
  • •AUX
  • •AUX activated
  • •AWT
  • •AWT activated
  • •Anticipatory Oil Pressure (AOP)
  • •Anticipatory Water Temperature (AWT)
  • •Auxiliary (AUX)
  • •Auxiliary fault
  • •Battery Charger Fault activated
  • •Controller fault
  • •Crank mode selection
  • •Emergency stop button pressed
  • •HWT
  • •HWT activated
  • •High Water Temperature (HWT)
  • •High engine temperature
  • •LF
  • •LOP
  • •LOP activated
  • •LWT
  • •Low Battery activated
  • •Low Fuel (LF)
  • •Low Fuel activated
  • •Low Oil Pressure (LOP)
  • •Low Water Temperature (LWT)
  • •Low oil pressure
  • •Low water temperature
  • •OC
  • •OC activated
  • •OS
  • •OS activated
  • •Overcrank
  • •Overcrank (OC)
  • •Overspeed
  • •Overspeed (OS)
  • •Remote start switch activated
  • •Remote switch activated

Suggested Actions

  1. 1Activate A/V alarm or common fault relay
  2. 2Connect A/V alarm or common fault relay kit
  3. 3Connect AV Alarm or Common Fault Relay Kit
  4. 4Connect TB1-2 to TB1-9 for continuous cranking
  5. 5Connect battery charger to TB1-61 to activate fault lamp (if used)
  6. 6Connect battery charger to TB1-62 to activate fault lamp (if used)
  7. 7Connect emergency stop across terminals TB1-1 and TB1-1A
  8. 8Connect fuel level sensor to TB1-63 to activate fault lamp (if used)
  9. 9Connect remote start switch to TB1-3 and TB1-4
  10. 10Leave TB1-9 open for cyclic cranking
  11. 11Remove jumper if Emergency Stop is used