2681
What This Code Means
Low fuel warning triggered; Fuel level at 20% or less; Extremely low fuel level warning; Diesel high fuel level warning; External warning indicator true; Fluid basin overfill indicator true; Fluid basin missing indicator true; Governor in open position for greater than one second; Command and position feedback not matching or taking too much time to achieve; Governor in closed position (commanded otherwise) for greater than one second; No message received for 1 second on CAN bus during startup; 12/24V Battery Type system mismatch; No response from I/O Extender 1 for 3 seconds; No response from I/O Extender 2 for 3 seconds; No response from I/O Extender 3 for 3 seconds; No response from I/O Extender 4 for 3 seconds; External Charger Fail digital input is True for 3 seconds while External Charger is enabled; Low fuel level switch triggered for 1 minute; Fuel Level is less than 10%
Possible Causes
- •Low fuel switch triggered for 1 minute
- •Fuel level is less than 10%
- •Fuel level above 90% full
- •Common warning indicator true for 1 second from configured external source I/O Extender
- •Fluid basin overfill indicator true for 1 second from configured external source I/O Extender
- •Fluid basin missing indicator true for 5 seconds from configured external source I/O Extender
- •Governor wire loose
- •Governor module
- •Problem with CAN bus interface
- •Dealer Config and the Digital Input for confirming a 12/24 V Battery Type system mismatch
- •Loss of communication with I/O Extender 1
- •Loss of communication with I/O Extender 2
- •Loss of communication with I/O Extender 3
- •Loss of communication with I/O Extender 4
- •External Charger Failure
- •Low fuel level (sensor triggers at 20% fuel remaining)
- •Extremely Low Fuel Level
Suggested Actions
- 1Review alarm log
- 2Address active alarms
- 3Inspect basin tank
- 4Contact technical service
- 5Test 68 – Check Actuator and Mixer Function page 163
- 6Test 106 – Test CAN bus Communication page 174
- 7Confirm battery type settings
- 8Inspect RS-485 wiring/terminating jumper on I/O
- 9Confirm external charger settings on controller menu
- 10Check external battery charger
- 11Check Fuel Level