0X05

UnclassifiedCooling

What This Code Means

AC breaker is OPEN or has tripped.; DC supplementary surge protector has expired.; DC breaker is OPEN or has tripped.; No other devices are found on SENSbus.; No module power boards are found on SENSbus.; Invalid configuration of one or more power modules in the unit.; A power module in the unit has faulted.; High Battery Temperature alarm; Unit has shut off for safety precautions due to high battery temperature; Charger's output ripple is above High AC Ripple Detection alarm setpoint; Charger has detected that the output is not connected to anything; Charger Low Temperature alarm; Battery Low Temperature alarm; An AC phase is missing or out of range; Maximum AC Voltage has gone above max AC voltage allowed by the charger on any phase; Output has been disabled; AC Voltage has gone below AC Min Voltage alarm setpoint; AC Frequency is outside of the AC High Frequency and AC Low Frequency alarm setpoints; AC Voltage is above the AC Max Voltage alarm setpoint; Settings for this channel are

Possible Causes

  • A power module in the unit has faulted.
  • AC Frequency is outside of the AC High Frequency and AC Low Frequency alarm setpoints
  • AC Voltage has gone below AC Min Voltage alarm setpoint
  • AC Voltage is above the AC Max Voltage alarm setpoint
  • AC breaker is OPEN or has tripped.
  • An AC phase is missing or out of range
  • Battery is connected backwards
  • Battery temperature is above the High Battery Temperature alarm setpoint
  • Battery temperature is below Battery Low Temperature alarm setpoint
  • Battery temperature is high enough
  • Channel Current is below Low Current alarm setpoint
  • Charger has detected that the output is not connected to anything
  • Charger output is not connected to anything
  • Charger's output ripple is above High AC Ripple Detection alarm setpoint
  • DC breaker is OPEN or has tripped.
  • DC supplementary surge protector has expired
  • DC supplementary surge protector has expired.
  • Invalid configuration of one or more power modules in the unit.
  • Maximum AC Voltage has gone above max AC voltage allowed by the charger on any phase
  • No module power boards are found on SENSbus.
  • No other devices are found on SENSbus.
  • Settings for this channel are invalid
  • Unit ambient temperature is below its rated ambient temperature

Suggested Actions

  1. 1Correct the battery connection polarity
  2. 2Replace DC supplementary surge protector.
  3. 3Replace the DC supplementary surge protector
  4. 4Reset Latched Alarms (Write 0xFF00 to coil 23 / 0x017)
  5. 5Settings must be corrected before settings may be sent to the chargers on this channel
  6. 6Unit output may be derated