000325A
UnclassifiedGeneral
What This Code Means
Caked or greasy dirt on generator; Dust and dirt on generator; Generator requires drying
Possible Causes
- •Accumulated dirt and grease
- •Dust accumulation
- •Water ingress into generator windings, terminals, or fuel system
Suggested Actions
- 1Loosen dirt with a soft brush or a damp cloth
- 2Use a vacuum system to clean up loosened dirt
- 3Remove dust and dirt using dry, low-pressure air of 25 psi (172.3 kPa) maximum
- 4Open the generator main circuit breaker.
- 5Disconnect all wires to completely disconnect the alternator.
- 6Provide an external source to blow warm, dry air through the generator interior (around the rotor and stator windings). Do not exceed 185 °F (85 °C).
- 7Connect stator lead.
- 8Start the generator and let it run for two or three hours.
- 9Shut down the generator and repeat the insulation resistance tests.